If you configure one of the dry contacts to act as a timer, the next step is to set the value of the timer.
Time can be entered in units of 0.5 second; e.g. 120 units of 0.5 seconds = 60 seconds. However, it is more

intuitive to enter time in the hh:mm:ss format, such as 00:01:00 for 1 minute or 60 seconds. Both methods

are shown in the following example.

Table K — Setting the Timer Contact

Enter command

UPS display

Description

Displaying the Timer

timer1 and press Enter

*timer1=02:00:00

Returns the value of Timer 1

timer2 and press Enter

*timer2=02:00:00

Returns the value of Timer 2

timer3 and press Enter

*timer3=02:00:00

Returns the value of Timer 3

Setting the

Timer

timer1=00:01:00 and press

Enter

*timer1=00:01:00

Sets the value of Timer 1 to 60

seconds.

timer1=120

and press

Enter

*timer1=120

timer2=00:01:00 and press

Enter

*timer2=00:01:00

Sets the value of Timer 2 to 60

seconds.

timer2=120

and press

Enter

*timer2=120

timer3=00:01:00 and press

Enter

*timer3=00:01:00

Sets the value of Timer 3 to 60

seconds.

timer3=120

and press

Enter

*timer3=120

default and press Enter

*default

Resets the timer to the factory

default of 02:00:00 (2 hours); and

resets contacts C1 to C5 to the

factory default settings.

Note: In the above example, the default timer setting of 2 hours is used.

* Indicates that the Alpha FXM has responded to the command you entered.

† Time can be entered in units of 0.5 second; e.g. 120 units of 0.5 seconds = 60 seconds. However, it is more intuitive

to enter time in the hh:mm:ss format, such as 00:01:00 for 1 minute or 60 seconds in the above example.