6.2.1  Line Mode

AC EMI

Battery

Input

Output(s)

Inverter/

Charger

120

INV

120

108

132

N

6.2.1.1  Boost Mode

When the input voltage drops, a reduction

in output voltage is prevented by increas-

ing the ratio of primary to secondary

windings in the transformer. The ratio is

increased by using a relay to change the

transformer taps.

6.2.1.2  Buck Mode

When the input voltage increases, an

increase in output voltage is prevented by

decreasing the ratio of primary to second-

ary windings in the transformer. The ratio

is decreased by using a relay to change

the transformer taps.

Input

120

108

132

N

120

INV

Input

120

108

132

N

120

INV

In line mode, the voltage input equals the voltage output. The FXM350 has Automatic Voltage Regulation

(AVR) to maintain the output voltage within the regulation range.

Grid relay

Grid relay

Grid relay