Table P — Fault Submenu

LCD Shows

Problem Description

What To Do

Overload Fault

The load draws more power than the

Alpha FXM can provide. This can lead

to an automatic Alpha FXM shutdown.

Remove excess loads.

Short Circuit

The load has a short.

Check the output. Remove the faulty

load if necessary.

Intl Temp Fault

The Alpha FXM internal temperature is

too high and could cause an automatic

Alpha FXM shutdown.

Verify that the fan is not blocked and

that it is working by performing a

battery test. Also See Fan Fail Alarm.

Output Over Voltage

The output voltage is above or below

the Alpha FXM specifications.

Info only.

Output Voltage Low

Battery Fail

In Inverter mode, the battery voltage

has dropped below a specified level.

This fault is triggered and the inverter

shuts down. This fault is also known

as a Low Battery Shutdown or Bad

Battery.

Info only. The Alpha FXM will recharge

the battery when the Alpha FXM

requalifies the line.

Backfeed

A relay inside the Alpha FXM has failed.

It cannot be fixed in the field.

DANGER:

Do NOT touch the AC input

terminals. Contact Alpha Technical

Support.

Battery Over Voltage

Battery voltage is abnormally high.

Check the voltage at the battery

voltage test points. Ensure that the

battery is in good working condition.

Replace the battery if necessary.

Batt Volt Low

Battery voltage is low and is close to

the self-kill level.

Ensure that the Alpha FXM charger is

working. If the charging voltage is low,

the battery may need to be replaced.

Table Q — Problems Not Reported by System

LCD Shows

Problem Description

What To Do

No LCD display even when the 

Alpha FXM is powered on

The LCD may not function below

-15ºC. This does not affect the normal

operation of the Alpha FXM

Bring the operating temperature

above -15ºC and the LCD display will

gradually resume operation.

Date and time reset to 00:01:00 and 

00:00:00 

The backup lithium coin battery may

need to be replaced. This is possible

if the Alpha FXM has been in storage

or switched off for a prolonged period.

The average operating life of the lithium

coin battery is about 5 years.

Replace the lithium coin battery.

Caution

: This must be performed by a

qualified service personnel. Dispose of

used batteries according to your local

laws and jurisdictions.