017-241-B0 Rev B

64

Figure 51 — User Input Configuration: Setting an Action

5. Select User Alarm On from the Action #1 drop down menu.

Figure 52 — User Input Current Status

Figure 53 — User Input Current Status

Perform a quick test by shorting the User Input 1 to SC (ground) with a short length of PVC insulated elec-

tronic wire. The Alpha FXM should issue a User Input Alarm .

Hovering the cursor over the amber indicator displays the corresponding context sensitive message.

6. Click the Update Configuration button and enter the password to confirm if required.

7. Check the User Input Current Status at the UPS Monitoring > User Input Status page.