7.2.2  The LCD Control Menu

The control menu (Table B) lets you operate the Alpha FXM or program it to suit your operating conditions.

7.2.2.1  Procedure

1. From the Logo screen press the SELECT button to go down to the CONTROL menu.

2. Press the SELECT button to enter the submenu (Table B).

3. Press the SCROLL button to move between items in the submenu.

4. When you have reached the item you want to change, press the SELECT button. The item chosen will

blink.

5. To toggle between the choices, press the SCROLL button. Stop when you reach the choice you want.

6. To make the change, press the SELECT button. The blinking stops.

Table B — Control Menu

LCD display

Meaning

Description

INVERTER

Inverter

When inverter mode is set to ON, the Alpha FXM provides backup battery power

to the load. This mode of operation is normally activated automatically when line

power becomes unavailable, or the line power is not qualified. You can also put

the Alpha FXM into this mode during initial startup in the absence of line power or

because of unqualified line power. See #31Inverter On/Off in Table I.

DC CONNECT

DC Output

Connect

Voltage

One of the dry contacts of the FXM350 can be programmed to operate as a

control for external DC disconnect and reconnect. (See LVD setting under "7.5.4

Programming the Dry Contacts" on page 82). The dry contact is energized when the

battery voltage is greater than the DC Connect set voltage and will de-energize if the

battery voltage drops below 42V for 48V system (21V for 24V system). The default

reconnect voltage is set to 48VDC and can be adjusted up to 51VDC.

BYPASS

Inverter

Bypass

This function can be enabled only when the Alpha FXM is in Line mode.

When enabled, the FXM locks into Line mode (no AVR) and disables the battery

charger. This mode is used when maintaining batteries.

OR

Allows the use of a break-before-make manual bypass switch so the Alpha FXM can

be shut off for maintenance without interrupting power to the load.

BATT TEST

Battery Test

Starts the battery test that uses depth-of-discharge setting that can be adjusted

using BT TS DOD menu.

BT TS DOD

Lets you set the desired battery test depth-of-discharge to a value between 0 and

100%. Make sure that the set time duration is shorter than the max back up time of

your battery bank. Otherwise, you will drain the battery and trigger a fault –

Batt Volt

Low. The default value is set to 20% DoD.

AUTO TEST

Automatic Test

Enable/Disable the scheduled self test.

SHUTDOWN

Shutdown AC

and DC

When this function is switched on, the Alpha FXM inverter is shut off. Neither Line

nor Inverter power is supplied to the load. If a dry contact was used as a LVD, the

LVD will open. See section 7.5.4.

SHUTDOWN AC

Shutdown AC

When this function is switched on, the Alpha FXM inverter is shut off. Neither Line

nor Inverter power is supplied to the load.

SHUTDOWN DC

Shutdown DC

When this function is switched on, the Alpha FXM DC output is shut off. Available

when dry contact C1 is programmed to be the Low Voltage Disconnect indicator.

See "7.5.4 Programming the Dry Contacts" on page 82.

SENSE TYPE

Sense Type

This function can only be used when the Alpha FXM is in Standby or Shutdown
mode—see

Table A for operating mode descriptions.

This function toggles between:

NORMAL: The Alpha FXM can operate successfully with most line conditions.

OR:

GENERATOR: The Alpha FXM input voltage and frequency parameters are

expanded so the Alpha FXM can work with the fluctuations caused by a generator or

noisy line.