Alpha Technologies FXM350_Micro350 UPS User Manual

Page 109

Advertising
background image

107

017-241-B0 Rev B

Level Alternative
When the level is set to High, the Alpha FXM is triggered to perform the next action when the user input

changes from Low to High. If the input then changes from High to Low, no action will be triggered because

the level is set to High. In other words, only a Low to High user input level triggers an action when Level is set

to High. Similarly, when Level is set to Low, the Alpha FXM will trigger an action only with a High to Low user

input.

Figure 74 — Level Alternative

User input

Action #1

Action #2

Action #1

Action #1

User input

Action #2

Action #1

User Input = Low to High, Action #1 is triggered

User Input = High to Low, no action triggered

User Input = Low to High, Action #2 is triggered

User Input = High to Low, no action triggered

User Input = High to Low, Action #1 is triggered

User Input = Low to High, no action triggered

User Input = High to Low, Action #2 is triggered

User Input = Low to High, no action triggered