7.2.4  Making Measurements

The System Status menu lets you make measurements of various Alpha FXM inputs, outputs, temperatures

and other values.

7.2.4.1  Procedure

1. From the Logo screen go to the SYSTEM STATUS menu.

2. Press the SELECT button to enter the submenu (Table C).

3. Press the SCROLL button to move between items in the submenu. When you reach the item you want

to measure, stop pressing the button. The measurement is automatically displayed on the LCD. It is

automatically updated every 0.5 seconds.

Table C — System Status Menu

LCD display

Meaning

Description

VIN

Input Voltage

The line input voltage into the Alpha FXM

VOUT

Output Voltage

The Alpha FXM output voltage (true RMS).

IOUT AC

Output Current

(AC)

The Alpha FXM AC output current (true RMS).

BATT TEMP

Battery

Temperature

The battery’s temperature (°C).

FREQ IN

Input Frequency

The frequency of line power into the Alpha FXM (Hz).

OUTPUT PWR

Output Power

The Alpha FXM output power in VA (true RMS).

BATT VOLT

Battery Voltage

The battery output voltage (VDC).

CHGR CUR

Charger Current

The Alpha FXM battery charging current is set to this value (Amps).

DATE

Displayed in the format set by the user.

TIME

Displayed in the format set by the user.

INV COUNT

# of line failures

Shows how many times the inverter has been active since the last time the

inverter counter was cleared. See INV RECORD description in Table B.

INV (min)

Amount of time

inverter was on

shows total time in minutes the inverter has been active since the last time

inverter timer was cleared. See INV RECORD description in Table B

SHED TIMER1

Amount of

time until the

dry contact is

activated.

The factory default dry contact for this setting is contact C4. SHED TIMER2 and

SHED TIMER3 can be field programmed. See “Setting the Timer Contact”. This

display shows the amount of time left in seconds until the contact is activated.

The factory default setting is 2 hours, but this can be changed as shown in

"Programming the Dry Contacts and the Clock". C4 is available on the FXM350 if

the optional signal assembly is installed—see Section 3.3.2.

SHED TIMER2

SHED TIMER3

MAC Address

Communication

Module's MAC

The Communication Module's MAC address is displayed.

IP Address

Communication

Module's IP

The Communication Module's IP is displayed.

kWh

kWh Meter

The accumulated output energy is displayed.

Remain Tm

Remaining

Battery Runtime

The remaining runtime of the battery is displayed. Refer to Appendix A to set

battery parameters.

Serial Number

Unit Serial

Number

The unit serial number of the Alpha FXM is displayed.

VERSION

Software Version

The software version used in this Alpha FXM