105
017-241-B0 Rev B
A.5 Using the Spreadsheet
Download the spreadsheet “Peukert’s Parameters Calculator.xls” from www.alpha.ca website.
Enter the Battery
voltage and
nominal load
From the data sheet of
the batteries enter the
2 closest currents and
discharge hours
Enter the
number of
parallel strings
}
CAUTION!
The battery runtime is only an estimation and must not be relied on for critical applica-
tions. The battery runtime remaining is applicable only in inverter/backup mode.