7.5.3  Adjusting and Controlling the Alpha FXM

Use submenu #3, the Maintenance submenu (Figure 67 and Figure 68) to control the Alpha FXM and

change selected items to meet your operational needs.

7.5.3.1 

From the Main menu, type 3 and press Enter.

Table I — Maintenance Submenu

30 Battery Test Options Starts the battery test and sets how long the test will run. The default setting for the test

depth-of-discharge is 20%, but this can be adjusted from 0 to 100%. For a description of

the battery test, see BATT TEST in Table B.

31 Inverter On/Off Switches the inverter on or off to allow you to prevent a damaging deep battery discharge

or to provide backup battery power to the load. For a description, see INVERTER in

Table B.

You can set a delay before the inverter switches off to allow time for switching off critical

loads. The Set Inverter ON/OFF delay is only available when the Alpha FXM is in the

Battery or Standby modes.

The delay can be adjusted in 1 second steps with a default setting of 0 seconds to a

maximum of 600 seconds (10 minutes). The delay is only available in the Standby or

Battery modes. Once the Alpha FXM returns to the Line mode, the delay resets itself to 0

seconds.

32 Change Password Changes the Alpha FXM password. The factory set password is 1111, which can only

be changed when the Alpha FXM is in Line mode. The password is limited to 4 alpha-

numeric characters in length.

34 Line Qualify Time Lets you set the delay when the Alpha FXM goes from Battery mode to Line mode after

the line becomes requalified. The purpose of this delay is to make sure the line is stable

before the Alpha FXM switches back to it. For a description, see QUAL TIME in Table B.

The default setting is 3 seconds, but you can set this to 3, 10, 20, 30, 40 or 50 seconds.

35 Low Battery Warning 

Voltage

Lets you set the Alpha FXM low battery warning voltage by typing in the % battery

voltage level where you want the warning to be triggered. Adjust the setting to match the

batteries you are using and the actual operating conditions.

48V

:

Default 40% -47 VDC

Adjusted in 1% increment – 0.05 VDC

Minimum 0% - 45.0

Maximum 100% - 50.0 VDC

24V

:

Default 40% - 23.5 VDC

Adjusted in 1% increment – 0.025 VDC

Minimum 0% - 22.5 VDC

Maximum 100% - 24.8 VDC

36 Load Shed Timer On/Off Lets you switch the timer contacts on or off. See "Contacts C1 to C2”.in section 2.3.