Appendix b - types of triggers, B.1 edge trigger, B.2 level toggle – Alpha Technologies FXM350_Micro350 UPS User Manual

Page 108

Advertising
background image

017-241-B0 Rev B

106

Appendix B - Types of Triggers

There are 3 types of trigger:

B.1  Edge trigger

When the user input changes from one state to the other, the Alpha FXM is triggered to perform Action #1. If

the level is set to High, the action will be triggered by a Low to High edge (leading edge). If the level is set to

Low, the action will be triggered by the High to Low edge (falling edge).

Figure 72 — Edge Trigger

B.2  Level Toggle

When the Level is set to High, the Alpha FXM is triggered to perform the other action when the user input

changes from Low to High. If the input then changes from High to Low, Action #2 will be triggered. In other

words, a level change in the user input will trigger an action toggle between Action #1 and #2.

Figure 73 — Level Trigger

Low to High

edge trigger

User input

Action #1

Action #1

(a) Level = High

User Input = Low to High, Action #1 is triggered
User Input = High to Low, no action triggered

High to Low

edge trigger

User input

Action #1

Action #1

(b) Level = Low

User Input = High to Low, Action #1 is triggered

User Input = Low to High, no action triggered

Action #1

Action #1

Action #2

Action #2

User input

(a) Level = High

User Input = Low to High, Action #1 is triggered

User Input = High to Low, Action #2 is triggered

Action #2

Action #2

Action #1

Action #1

User input

(b) Level = Low

User Input = High to Low, Action #1 is triggered

User Input = Low to High, Action #2 is triggered

Advertising