5.3  Wiring the External Batteries and Optional Battery Heater Mats

WARNING!

The batteries must be installed by qualified personnel trained in the safe use of high-

energy power supplies and their batteries. Refer to the safety section in this manual.

• Use new batteries when installing a new unit. Verify that all batteries are the same type with identical

date codes.

• Use appropriate battery voltage string for 24 and 48V versions of the products.
• If you are making your own battery wiring harness, use at least 10 AWG wires.
• The battery return connection is to be treated as an Isolated DC return (DC-I) as defined in GR-1089-

CORE.

5.3.1  Procedure

1. Place the battery heat mat(s) on the battery shelves. Refer to the manual that ships with the battery heat

mat to connect it to a power source.

2. For FXM350-48 (48V battery string), number the batteries from 1 to 4 with labels or tape. For FXM350-24

(24V battery string), number the batteries from 1 to 2 as shown in the Figure 22.

3. Coat the battery terminals with the corrosion inhibitor.

Battery #4

Battery #3

Battery #2

Battery #1

To positive terminal

To negative terminal

Optional in-line fuse

Figure 22 — External Battery Wiring (for 48 VDC string (top) and 24 VDC string)