Alpha Technologies FXM350_Micro350 UPS User Manual

Page 88

Advertising
background image

017-241-B0 Rev B

86

7.5.6  Viewing the Serial Number

To display the serial number of the Alpha FXM UPS, type "∗QY0" at the command line and press "Enter".

7.5.7  Setting the Peukert Number and Capacity

You can set the Peukert Number and Capacity using the USBinterface or the web interface. To display the

current Peukert Number, type "∗QY6" at the command line and press "Enter".

To change the Peukert Number to 1.1345, type "∗ST6:1.1345" at the command line and press "Enter".

To display the current Peukert Capacity, type "∗QY7" at the command line and press "Enter".

To change the Peukert Capacity to 109.123, type "∗ST7:109.123" at the command line and press "Enter".

To determine the Peukert number and capacity of your battery, refer to "Appendix A - Puekert Number and

Battery Capacity" on page 103.

Advertising