1 operating modes – Alpha Technologies FXM350_Micro350 UPS User Manual

Page 45

Advertising
background image

43

017-241-B0 Rev B

7.2.1  Operating Modes

The Alpha FXM operating mode, (see Table A) automatically changes as a result of changes in the line. Refer

to Chapter 10, Specifications, for Boost/Buck/Line transfer thresholds. The LCD panel automatically updates

to reflect the change.

Table A — UPS Operating Modes

LCD display

Description

SHUTDOWN

The Alpha FXM inverter is switched off. Line power is disconnected from the load.

LINE

The Alpha FXM is switched on. Line power is provided to the load.

BOOST1

When the input voltage is lower than the nominal voltage, the Alpha FXM raises line voltage

without using the batteries. Automatic voltage regulation (AVR) is enabled.

BUCK1

The Alpha FXM lowers line voltage without using the batteries. AVR is enabled.

INVERTER

The Alpha FXM is providing backup battery power to the load. See INVERTER in Table B

on page 45.

RETRAN

The Alpha FXM is transferring from INVERTER mode to Line mode.

TRAN

The Alpha FXM is transferring from the state it is now in into Inverter mode.

STANDBY

The Alpha FXM is switched on and waiting for the line power to be qualified or the user to

clear some faults.

CAUTION: Do not touch the AC output terminals; they may still be energized.

BYPASS

This mode is manually set from the Control Menu. See Figure 28, “Control Menu, INV

BYPASS”. This locks the unit into line mode and turns off the battery charger so the unit can

work with a manual break-before-make bypass switch. AVR will be disabled.