Troubleshooting, 1 procedure – Alpha Technologies FXM350_Micro350 UPS User Manual

Page 98

Advertising
background image

017-241-B0 Rev B

96

9.  Troubleshooting

When the front panel alarm LED is illuminated or flashing, the Alpha FXM has a malfunction:
• Red LED solidly illuminated indicates a fault in the Alpha FXM. (See Table P.)
• Red LED flashing indicates an alarm. ( See Table O.)
The web interface can also be used for troubleshooting.

9.1  Procedure

1. Press the SELECT button.

2. The LCD may display one or more of the conditions in Table O.

3. Press the SCROLL button to see if more than one malfunction is present.

4. To clear the malfunction from the screen, press and hold the SELECT button for 5 seconds.

Table O — Alarm Submenu

LCD Shows

Problem Description

What To Do

Over Load

The Alpha FXM is overloaded.

Remove excess loads.

Batt Temp High

The battery temperature is above the

specification limit.

If used, ensure that the battery fan is

working. Contact Alpha Technical Support to

purchase an upgrade if required.

Batt Temp Low

The battery temperature is below the

specification limit.

Use optional battery heating mats or heater.

Contact Alpha technical support to place the

order.

Batt Low Warning

The batteries are almost discharged.

Also see “Adjusting and Controlling the

Alpha FXM, #35: Low Battery Warning

Voltage”.

Check that the DC breaker is closed.

Ensure that the Alpha FXM charger is

working. If the charging voltage is low, the

battery may need to be replaced.

FAN Alarm

The fan has failed.

Contact Alpha technical support. The fan is

not a replaceable part.

Temp Probe Unplug

The temperature probe is unplugged.

Plug it back into the Alpha FXM or change

the probe.

User Input Alarm

When the user input is shorted. See “User

Input: S2”.

Check the user input parameters.

In Freq Out Of Range

The line frequency is outside of the

Alpha FXM allowable range. The Alpha FXM

goes into Inverter mode.

Info only.

Weak Battery

The battery is being monitored continuously

in the background in Line mode. This alarm

is issued if the battery did not pass the

background scan.

Check the battery life and replace the

battery if necessary.

Battery Test

The Alpha FXM is performing a battery test.

Info only.

Invalid Software

The FXM software is invalid (either version or

part number.

Contact Alpha technical support.

Keep Alive Failure

The Alpha FXM failed to restore

communication by resetting power using

keep alive feature.

Turning off keep the alive feature will clear

the alarm.