Alpha Technologies FXM350_Micro350 UPS User Manual

Page 82

Advertising
background image

017-241-B0 Rev B

80

7.5.2.4  Main Menu Screen — Fault and Alarm Displays

Faults and alarms display on the main menu screen. See Chapter 9, Troubleshooting.

Table G — Faults (see Figure 67)

Short_Circuit The load has a short.

Vout_Hi The output voltage is above specifications.

Batt_Hi The batteries cannot be charged.

Batt_Lo The batteries are almost discharged.

Vout_Lo The output voltage is below specifications.

Overload The Alpha FXM is overloaded. Remove excess loads.

Backfeed A relay inside the Alpha FXM has failed and it cannot be replaced in the field. Contact

Alpha Technologies customer service department.

Bad_Battery The battery voltage has dropped below a specified level. Inverter shuts down.

Temp_Hi The Alpha FXM is operating above temperature range.

Table H — Alarms (see Figure 67)

AC_Brkr_Open The AC breaker is opened.

Batt_Brkr_Open The battery breaker is opened.

Batt_Low The battery voltage is low.

Fan_Fail The Alpha FXM internal fan has failed.

Keep_Alive The Alpha FXM keep alive feature failed to restore communication.

Line_Freq The line frequency is outside of the Alpha FXM input specifications.

No_Temp_Probe The battery temperature sensor has become disconnected or has failed.

Overload The Alpha FXM is overloaded. Switch off excess loads.

Self_test The Alpha FXM is performing self test.
Temp_Hi The ambient battery temperature is too high.

Temp_Lo The ambient battery temperature is too low.

User_Input The user input contact "User Input: S2" is shorted.

Weak_Battery The battery has failed the background scan in Line mode.

Wrong_Software The Alpha UPS Monitor is invalid (either version or part number).