017-241-B0 Rev B

5.1.2.1  Procedure

1. Remove the front cover of the enclosure – lift

the cover up and then pull out at the bottom.

2. If necessary, remove the knockouts with a

hammer and screwdriver.

3. If used, install conduits into the openings.

4. Install the wires into the cabinet. Make sure

that the wiring is long enough to reach the

terminal blocks.

5. Strip the ends of the wires by 7/16" (11 mm).

6. Run the ground wire to the ground terminal

shown in Figure 17.

7. Push in the button on the terminal block and

then insert each wire into the corresponding

terminal. See Figure 18.

8. Secure the wiring to the wiring management

panel with tie-wraps provided with the

Micro350.

9. Remove the packaging around the door

switch after completing the wiring.

Figure 17 — Wiring the Micro350

The input and output wiring must NOT touch the cabinet except for the wiring manage-

ment panel.
The input terminal block has two inputs for each pole (line, neutral and ground). Make

sure you have inserted each wire into the correct position and not accidentally connect-

ed the line and neutral to the same pole.
Verify the line wire is attached to the line terminal block, the ground wire is attached to

the ground terminal block and the neutral wire is attached to the neutral terminal block

to prevent accidental shocks or electrocutions.

WARNING!

CORRECT

INCORRECT

Figure 18 — Terminal block wiring

Factory installed

ground wire.

Remove knockouts for wiring.

Connect ground

wire to copper-

ground terminal.