Command set – Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 121

Advertising
background image

Command Set


4-18 ADAM 4000 Series User’s Manual

ADAM-4018+ Command Table

Command Syntax

Command Name

Command Description

Page No.

%AANNTTCCFF

Configuration

Set the address, input range, baud
rate, data format, checksum status
and/or integration time for the
specified analog input module

5-4

$AA2

Configuration Status

Return the configuration
parameters for the specified analog
input module

5-10

$AAF

Read Version

Return the firmware version code
from the specified analog input

module

5-12

$AAM

Read Module Name

Return the module name from the
specified analog input module

5-13

#AA Read

Analog

Input

from all Channels

Return the input value from all
channels of the specified analog
module

5-14

#AAN Read

Analog

Input

from Channel N

Return the input value from
channels number N of the
specified analog input module

5-16

$AA5VV Enable/disable

Channels for
Multiplexing

Enables/disables multiplexing
simultaneously for seperate
channels of the specified input
module

5-17

$AA6 Read

Channel

Status

Ask the specified input module to
return the status of all eight
channels

5-18

$AAB

Get Operating Status

Get the channel operating status When
bit value is 0, it mean this channel is in
normal operating, when bit value is 1, it
mean this channel is opening wire

5-24

$AA3

CJC Status

Returns the value of the CJC
sensor for a specified analog input
module

5-25

$AA9SNNNN

CJC Offset
Calibration

Calibrates an analog input module to
adjust for offset errors of its CJC
sensors

5-26

$AA0Ci Span

Calibration

Gain error calibrate of assignment
channel, User have to input the external
standard source for calibrating process

5-27

(Continued on following page)