Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 345
Advertising

Appendix A
Appendix A Technical Specification A-17
Table A-10 ADAM-4018/4018+ Range Accuracy for
Thermocouple
Input
Range
Code
(Hex)
Input Range
Typical
Accuracy
Maximum
Error
Units
0E
J thermocouple
0 to 760 ℃
±1.0 ±1.5
℃
0F
K thermocouple
0 to 1370 ℃
±1.0 ±1.5
℃
10
T thermocouple
-100 to 400 ℃
±1.0 ±1.5
℃
11
E thermocouple
0 to 1000 ℃
±1.0 ±1.5
℃
12
R thermocouple
500 to 1750 ℃
±1.2 ±2.5
℃
13
S thermocouple
500 to 1750 ℃
±1.2 ±2.5
℃
14
B thermocouple
500 to 1800 ℃
±2.0 ±3.0
℃
NOTE: Because the CJC sensor of ADAM-4018 is located in
the side of channel 0 to 4, the measurement will have the
difference ± 1 ℃ between channel 0 ~ 4 and channel 5 ~ 7.