3 digital i/o, alarm and event command set – Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 193

Chapter
5
5-47
ADAM 4000 Series User’s Manual
5.3 Digital I/O, Alarm and Event Command Set
Command Syntax
Command Name
Description
I/O Module
@AADI
Read Digital I/O and
Alarm Status
The addressed module
returns the state of its digital
input and digital output
channels and the status of its
alarm
4011, 4011D,
4012, 4016
@AADO(data) Set
Digital
Output
Values
Set the values of the
module's digital outputs (ON
or OFF)
4011, 4011D,
4012, 4016
@AAEAT
Enable Alarm
Enables the alarm in either
Momentary or Latching mode
4011, 4011D,
4012, 4016
@AAHI(data)
Set High Alarm Value Downloads the High alarm
limit value
4011, 4011D,
4012, 4016
@AALO(data)
Set Low Alarm Value
Downloads the Low alarm
limit value
4011, 4011D,
4012, 4016
@AADA Disable
Alarm
Disables
all
alarm
functions
4011,
4011D,
4012, 4016
@AACA
Clear Latch Alarm
Resets the module's Latch
alarm to zero
4011, 4011D,
4012, 4016
@AARH Read
High
Alarm
Value
Ask the addressed module to
return its high alarm value
4011, 4011D,
4012, 4016
@AARL Read
Low
Alarm
Value
Ask the addressed module to
return its low alarm value
4011, 4011D,
4012, 4016
@AARE
Read Event Counter
Ask the addressed module to
return its event counter value
4011, 4011D,
4012
@AACE
Clear Event Counter
Reset the module's event
counter to zero
4011, 4011D,