Utility Software

D-6 ADAM 4000 Series User’s Manual

D.2 The procedure for ADAM-4000 series installation guide

When user first time gets ADAM-4000 modules, he can refer following
procedure to configure and operate. Especially note that new ADAM-4000
modules will have default factory settings with Address setting 1, and data
format 9600, N, 8, 1. Redefine the address to avoid ID conflict if two or
more new modules
are used in the same network.

Standard Installation Procedures

1. Prepare the install environment

• Host computer

• Isolated RS-232/RS-485 Converter

• ADAM module

2. Install ADAM-4000-5000 utility in host computer

3. Wiring for ADAM-4000 module

Power supply & Communication Wiring

4.

Move hardware switch to Initial mode (For some older Adam models,

use an external wire to connect the INIT* terminal to the GND
terminal.

Booting the module while connecting the INIT* terminal with

the module’s GND terminal forces the configuration into a known state
called the INIT* state.)