Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 149

Chapter
5
5-3
ADAM 4000 Series User’s Manual
Command
Syntax
Command Description
I/O Module
$AA4
Returns the value that was
stored in the specified module's
register after the #** command
4011, 4011D, 4012, 4013, 4015,
4015T, 4016
$AAB
Ask the module to respond
whether the wiring is open or
closed
4011D, 4015, 4015T, 4018+,
4019+
$AA3
Returns the value of the CJC
sensor for a specified analog
input module
4011, 4011D, 4018, 4018+,
4018M, 4019+
$AA9
Calibrates the CJC sensor for
offset errors
4011, 4011D, 4018, 4018+, 4018M
4019+
$AA0Ci
Calibrates a specified channel
to correct for gain errors
4015, 4015T, 4017+, 4018+, 4019+
$AA1Ci
Calibrates a specified channel
to correct for offset errors
4015, 4015T, 4017+, 4018+, 4019+
$AA7CiRrr
Configure the input type and
range of the specified channel
in an analog input module
4015, 4015T, 4017+, 4018+, 4019+
$AA8Ci
Get the input type and range of
the specified channel in an
analog input module
4015, 4015T, 4017+, 4018+, 4019+
$AAXnnnn
Communication Watchdog Timer
Setting
4015, 4015T, 4017+, 4018+,4019+
$AAY
Read Communication Watchdog
Timer Setting
4015, 4015T, 4017+, 4018+, 4019+
$AAS0
Internal self-calibration for offset
and gain errors
4015, 4015T
$AAS1 Reload
factory
default
calibrating parameter to
overwrite current calibrating
parameter
4015, 4015T