Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 149

Advertising
background image

Chapter

5


5-3

ADAM 4000 Series User’s Manual

Command
Syntax

Command Description

I/O Module

$AA4

Returns the value that was
stored in the specified module's
register after the #** command

4011, 4011D, 4012, 4013, 4015,
4015T, 4016

$AAB

Ask the module to respond
whether the wiring is open or
closed

4011D, 4015, 4015T, 4018+,
4019+

$AA3

Returns the value of the CJC
sensor for a specified analog
input module

4011, 4011D, 4018, 4018+,
4018M, 4019+

$AA9

Calibrates the CJC sensor for
offset errors

4011, 4011D, 4018, 4018+, 4018M
4019+

$AA0Ci

Calibrates a specified channel
to correct for gain errors

4015, 4015T, 4017+, 4018+, 4019+

$AA1Ci

Calibrates a specified channel
to correct for offset errors

4015, 4015T, 4017+, 4018+, 4019+

$AA7CiRrr

Configure the input type and
range of the specified channel
in an analog input module

4015, 4015T, 4017+, 4018+, 4019+

$AA8Ci

Get the input type and range of
the specified channel in an
analog input module

4015, 4015T, 4017+, 4018+, 4019+

$AAXnnnn

Communication Watchdog Timer
Setting

4015, 4015T, 4017+, 4018+,4019+

$AAY

Read Communication Watchdog
Timer Setting

4015, 4015T, 4017+, 4018+, 4019+

$AAS0

Internal self-calibration for offset
and gain errors

4015, 4015T

$AAS1 Reload

factory

default

calibrating parameter to
overwrite current calibrating
parameter

4015, 4015T

Advertising