Data formats and i/o ranges, B.2 analog input ranges – Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 382

Data Formats and I/O Ranges
B-6 ADAM 4000 Series User’s Manual
B.2 Analog Input Ranges
Range
Code
(hex)
Input Range
Description
Data Formats
+F.S.
Zero
-F.S.
Displayed
Resolution
00 ±
15
mV
Engineering
Units
+15.000 ±00.000 -15.000
1
µv
% of FSR
+100.00
±000.00
-100.00
0.01%
Twos
Complement
7FFF 0000 8000 1
LSB*
01 ±
50
mV
Engineering
Units
+50.000 ±00.000 -50.000
1
µv
% of FSR
+100.00
±000.00
-100.00
0.01%
Twos
Complement
7FFF 0000 8000 1
LSB*
02 ±
100
mV
Engineering
Units
+100.00 ±000.00 -100.00
10
µv
% of FSR
+100.00
±000.00
-100.00
0.01%
Twos
Complement
7FFF 0000 8000 1
LSB*
03 ±
500
mV
Engineering
Units
+500.00 ±000.00 -500.00
10
µv
% of FSR
+100.00
±000.00
-100.00
0.01%
Twos
Complement
7FFF 0000 8000 1
LSB*
04
± 1 V
Engineering
Units
+100.00 ±0.0000 -1.0000
100.00
µv
% of FSR
+100.00
±000.00
-100.00
0.01%
Twos
Complement
7FFF 0000 8000 1
LSB*
05
± 2.5 V
Engineering
Units
+2.5000 ±0.0000 -2.5000
100.00
µv
% of FSR
+100.00
±000.00
-100.00
0.01%
Twos
Complement
7FFF 0000 8000 1
LSB*
06 ±
20
mV
Engineering
Units
+20.000 ±00.000 -20.000
1
µv
% of FSR
+100.00
±000.00
-100.00
0.01%
Twos
Complement
7FFF 0000 8000 1
LSB*
07 ±
4~20mA
Engineering
Units
+20.000 ±00.000 -20.000
1
µA
% of FSR
+100.00
±000.00
-100.00
0.01%
Twos
Complement
7FFF 0000 8000 1
LSB*