Data formats and i/o ranges, B.2 analog input ranges – Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 382

Advertising
background image

Data Formats and I/O Ranges

B-6 ADAM 4000 Series User’s Manual

B.2 Analog Input Ranges

Range
Code
(hex)

Input Range
Description

Data Formats

+F.S.

Zero

-F.S.

Displayed
Resolution

00 ±

15

mV

Engineering
Units

+15.000 ±00.000 -15.000

1

µv

% of FSR

+100.00

±000.00

-100.00

0.01%

Twos
Complement

7FFF 0000 8000 1

LSB*

01 ±

50

mV

Engineering
Units

+50.000 ±00.000 -50.000

1

µv

% of FSR

+100.00

±000.00

-100.00

0.01%

Twos
Complement

7FFF 0000 8000 1

LSB*

02 ±

100

mV

Engineering
Units

+100.00 ±000.00 -100.00

10

µv

% of FSR

+100.00

±000.00

-100.00

0.01%

Twos
Complement

7FFF 0000 8000 1

LSB*

03 ±

500

mV

Engineering
Units

+500.00 ±000.00 -500.00

10

µv

% of FSR

+100.00

±000.00

-100.00

0.01%

Twos
Complement

7FFF 0000 8000 1

LSB*

04

± 1 V

Engineering
Units

+100.00 ±0.0000 -1.0000

100.00

µv

% of FSR

+100.00

±000.00

-100.00

0.01%

Twos
Complement

7FFF 0000 8000 1

LSB*

05

± 2.5 V

Engineering
Units

+2.5000 ±0.0000 -2.5000

100.00

µv

% of FSR

+100.00

±000.00

-100.00

0.01%

Twos
Complement

7FFF 0000 8000 1

LSB*

06 ±

20

mV

Engineering
Units

+20.000 ±00.000 -20.000

1

µv

% of FSR

+100.00

±000.00

-100.00

0.01%

Twos
Complement

7FFF 0000 8000 1

LSB*

07 ±

4~20mA

Engineering
Units

+20.000 ±00.000 -20.000

1

µA

% of FSR

+100.00

±000.00

-100.00

0.01%

Twos
Complement

7FFF 0000 8000 1

LSB*






Advertising