Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 186

Advertising
background image




5-40

ADAM 4000 Series User’s Manual

4018M

@AAL

Name

Event Record Count command

Description

Request the number of event records stored in the analog
input data logger at address AA.

Syntax

@AAL (cr)

@

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of an analog input data logger.

L

is the Event Record Count command.

(cr)

is the terminating character, carriage return (0Dh).

Response

!AAHHHH(cr)

if the command is valid.

!

is a delimiter character indicating a valid command was

received.

AA

(range 00-FF) represents the 2-character hexadecimal

address of an analog input module.

HHHH

represents the 4-character hexadecimal number of

event records stored in the analog input data logger at
address AA.

(cr)

is the terminating character, carriage return (0Dh).

Example

command: @F3L(cr)
response: !F30096(cr)

The command requests the number of event records stored
in the analog input data logger at address F3.

The module currently has 150 event records.