Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 267

Advertising
background image

Digital I/O and Relay Output

Counter/Frequency Command Set


7-32 ADAM 4000 Series User’s Manual

$AAF

Name Read

Version

command

Description

The command requests the analog input module at address
AA to return the version code of its firmware.

Syntax

$AAF (cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address that you will access to.

F

is the Read Version command.

(cr)

is the terminating character, carriage return (0Dh).

Response

!AA(Version)(cr)

if the command is valid.

There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.

!

is a delimiter character which indicates a valid command.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the module.

(Version)

is the version code of the module's firmware at

address AA.

(cr)

is the terminating character, carriage return (0Dh).

4080, 4080D