5-68

ADAM 4000 Series User’s Manual

4016

$AAB

Name Span

Calibration

command

Description

Stores the voltage output value of the addressed strain
gauge input module as 10V reference.

Syntax

$AAB(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the strain gauge input module whose output
channel is to be calibrated.

B

is the Span Calibration command.

(cr)

is the terminating character, carriage return (0Dh).

Response

!AA(cr)

if the command is valid.

?AA(cr)

if an invalid command was issued.

There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.

!

delimiter character indicates a valid command was

received.

?

delimiter character indicates the command was invalid.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the strain gauge input module.

(cr)

is the terminating character, carriage return (0Dh).

Before issuing the Span Calibration command, the analog
output should be trimmed to the correct value with the
Trim Calibration command. A voltmeter should be
connected to the module’s output channel. (See also the
strain gauge input module’s Trim Calibration command
and Chapter 8, Calibration, for a detailed description.)