Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 130

Advertising
background image

Chapter

4


Chapter 4 Command Set 4-27


ADAM-4050 Command Table

Command Syntax

Command Name

Command Description

Page
No.

%AANNTTCCFF

Configuration

Sets address, baud rate, and/or
checksum status, to a digital I/O
module

7-4

$AA6

Digital Data In

Returns the values of the digital I/O
channels of the addressed module

7-6

#AABB(data)

Digital Data Out

Writes specified values to either a
single channel or all channels
simultaneously

7-8

#** Synchronized

Sampling

Orders all digital I/O modules to
sample their input values and store
them in a special register

7-11

$AA4 Read

Synchronized
Data

Return the value of a specified digital
I/O module that was stored after an
#** command was issued

7-12

$AA2 Configuration

Status

Returns the configuration parameters
of a specified digital I/O module

7-14

$AA5

Reset Status

Indicates whether a specified digital
I/O module was reset after the last
time the $AA5 command was issued

7-16

$AAF Read

Firmware

Version

Return the firmware version code
from the specified digital I/O module

7-18

$AAM Read

Module

Name

Return the module name from the
specified Digital I/O module

7-19


















Advertising