Advantech Data Acquisition Modules ADAM 4000 User Manual
Page 340

Technical Specifications
A-12 ADAM 4000 Series User’s Manual
A.5 ADAM-4016 Analog Input/Output Module
Table A-7 ADAM-4016 Specifications
AI channel number
1
AI range
±15 mV, ±50 mV, ±100 mV, ±500 mV
and ±20 mA
Output
Speed (bps)
Maximum distance
RS-485 (2-wire)
1200, 2400, 4800, 9600, 19.2K, 38.4K,
57.6K, 115.2K
4000 ft. (1200 m)
Input impedance
Voltage: 2 MΩ, Current: 125 Ω
AI isolation voltage 3000
V
DC
AI resolution
16-bit
AI sampling rate
10 samples/second
AI accuracy
±0.05% or better
AI zero drift
±6 μV /℃
AI span drift
±25 ppm/℃
AI CMR @ 50/60 Hz
150 dB
AI NMR @ 50/60 Hz
100 dB
AO channel number
1
AO range
0~10 V
AO drive current
30 mA
AO isolation voltage
3000 V
DC
AO accuracy
0.05% of FSR
AO drift
± 50 ppm/℃
Digital output
Sink current
Power dissipation
4 channels open collector to 30 V
30 mA maximum load
300 mW
Support protocol
ADAM ASCII
Watchdog timer
1.6 second (System)
Power requirements
+10 to +30 V
DC
(non-regulated)
Power consumption
2.2 W @ 24 V
DC