6-5 ADAM 4000 Series User’s Manual

%AANNTTCCFF

Example command:

%310A310610(cr)

response: !24(cr)

The analog input module is configured from addresses 31h
to a new address 0Ah, output range 4 to 20 mA, baud rate
9600, engineering units data format, a slew rate of 1.0
mA/sec and no checksum checking.

The response indicates that the command has been
received.