5-6
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
Table 5-1 Input Range Codes (Type Codes)
Input Range Code (Hex)
Input Range for 4011, 4011D, 4018, 4018+
(Thermocouple and ± 20 mA only), 4018M
00
± 15 mV
01
± 50 mV
02 ±
100
mV
03 ±
500
mV
04 ±
1
V
05 ±
2.5
V
06
± 20 mA
0E
Type J Thermocouple 0 ~ 760 ℃
0F
Type K Thermocouple 0 ~ 1370 ℃
10
Type T Thermocouple -100 ~ 400 ℃
11
Type E Thermocouple 0 ~ 1000 ℃
12
Type R Thermocouple 500 ~ 1750 ℃
13
Type S Thermocouple 500 ~ 1750 ℃
14
Type B Thermocouple 500 ~ 1800 ℃
Input Range Code(Hex)
Input Range for 4012,4017,4017+
08
± 10 V
09
± 5 V
0A
± 1 V
0B ±
500
mV
0C ±
150
mV
0D
± 20 mA
Notice: The input range requires the usage of a 125 Ω current conversion resistor
Input Rage Code (Hex)
Input Range for 4016
00 ±15
mV
01 ±50
mV
02 ±100
mV
03 ±500
mV
06 ±20
mA