Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 152

Advertising
background image




5-6

ADAM 4000 Series User’s Manual

4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+

Table 5-1 Input Range Codes (Type Codes)

Input Range Code (Hex)

Input Range for 4011, 4011D, 4018, 4018+

(Thermocouple and ± 20 mA only), 4018M

00

± 15 mV

01

± 50 mV

02 ±

100

mV

03 ±

500

mV

04 ±

1

V

05 ±

2.5

V

06

± 20 mA

0E

Type J Thermocouple 0 ~ 760 ℃

0F

Type K Thermocouple 0 ~ 1370 ℃

10

Type T Thermocouple -100 ~ 400 ℃

11

Type E Thermocouple 0 ~ 1000 ℃

12

Type R Thermocouple 500 ~ 1750 ℃

13

Type S Thermocouple 500 ~ 1750 ℃

14

Type B Thermocouple 500 ~ 1800 ℃

Input Range Code(Hex)

Input Range for 4012,4017,4017+

08

± 10 V

09

± 5 V

0A

± 1 V

0B ±

500

mV

0C ±

150

mV

0D

± 20 mA

Notice: The input range requires the usage of a 125 Ω current conversion resistor

Input Rage Code (Hex)

Input Range for 4016

00 ±15

mV

01 ±50

mV

02 ±100

mV

03 ±500

mV

06 ±20

mA

Advertising