Name

Synchronized Sampling command

Description

Orders all (analog or digital) input modules to sample their
input values and store them into a special register.

Syntax

#**

#

is a delimiter character.

**

is the Synchronized Sampling command.

The terminating character, in the form of a carriage
return (0Dh), is not required.

Response

The digital I/O modules will not respond to the
Synchronized Sampling command. In order to retrieve the
data, you must execute a Read Synchronized Data
command for every module separately.