Normal operating conditions, Accessories, Model and suffix code – Yokogawa AXFA14G/C User Manual

Page 106

Advertising
background image

IM 01E20C02-01E

11-4

11. OUTLINE

Safety Requirement Standards:

EN61010-1

• Altitude at installation site: Max. 2000 m above sea level
• Installation category based on IEC1010:

Overvoltage category II (“II” applies to electrical equip-
ment which is supplied from a fixed installation-like
distribution board.)

• Pollution degree based on IEC1010

Pollution degree 2 (“Pollution degree” describes the
degree to which a solid, liquid, or gas which deteriorates
dielectric strength or surface resistivity is adhering. “2”
applies to a normal indoor atmosphere.)

EMC Conformity Standards:

,

EN61326-1 Class A, Table 2 (For use in industrial locations)
EN61326-2-3
EN61000-3-2 ClassA
EN61000-3-3

CAUTION

This instrument is a Class A product, and it is
designed for use in the industrial environment. Please
use this instrument in the industrial environment only.

NORMAL OPERATING CONDITIONS

Ambient Temperature: –40

°C to +60°C (–40°F to +140°F)

• Indicator’s operating range: –20

°C to +60°C (–4°F to +140°F)

• Maximum temperature should be 50

°C in the case of

power supply code 2.

Ambient Humidity: 0 to 100%

Lengthy continuous operation at 95% or more is not
recommended.

Power Supply

Power supply code 1:

• AC specifications

Rated power supply: 100 to 240 V AC, 50/60 Hz
(Operating voltage range: 80 to 264 V AC)

• DC specifications

Rated power supply: 100 to 120 V DC
(Operating voltage range: 90 to 130 V DC)

Power supply code 2:

• AC specifications

Rated power supply: 24 V AC, 50/60 Hz
(Operating voltage range: 20.4 to 28.8 V AC)

• DC specifications

Rated power supply: 24 V DC
(Operating voltage range: 20.4 to 28.8 V DC)

Supply Voltage and

Cable Length for Power Supply Code 2

0

20.4

22

24

26

28.8

200 ( 660)

446 (1460)

600 (1970)

796 (2610)

F04.EPS

Cable cross section area: 1.25 mm

2

Cable cross section area: 2 mm

2

Allo

w

ab

le cab

le length m(ft)

Usable range E (V)

Vibration Conditions:

Level of vibration in conformity with IEC 60068-2-6
(SAMA31. 1-1980)

9.8 m/s

2

or less (frequency of 500 Hz or less)

Note: Avoid locations with much vibration (with a vibration

frequency of 500 Hz or more), which may cause
damage to the equipment.

ACCESSORIES

Mounting bracket: 1 set
Hexagonal wrench: 1 pc.

MODEL AND SUFFIX CODE

AXFA14 Magnetic Flowmeter Remote Converter:

Model

Suffix Code

Description

1

2

N

*1:

T03.EPS

G · · · · · · · · · · · · · · ·

C · · · · · · · · · · · · · · ·

-D · · · · · · · · · · · ·

-E · · · · · · · · · · · ·

-F · · · · · · · · · · · ·

-G · · · · · · · · · · · ·

1 · · · · · · · · ·
2 · · · · · · · · ·

1 · · · ·
2 · · · ·

N · · · ·

-0 · · · · · ·
-2 · · · · · ·
-4 · · · · · ·

4 to 20 mA DC, BRAIN Communication
4 to 20 mA DC, HART Communication
Digital communication
(F

OUNDATION

Fieldbus protocol)(*5)

Digital communication
(PROFIBUS PA protocol)(*6)

Magnetic Flowmeter Remote Converter

JIS G1/2 female
ANSI 1/2 NPT female
ISO M20

ϫ 1.5 female

General-Purpose Use
For AXF Remote Flowtube of Size
2.5 to 400 mm (0.1 in. to 16 in.)

Explosion proof Type
For Remote Flowtube of Size 2.5 to
400 mm (0.1 in. to 16 in.)

100 V to 240 V AC or 100 to 120 V DC
24 V AC/DC

With Indicator (Horizontal)
With Indicator (Vertical)
None

/

ٗ Optional code (See the Table of

Optional Specifications)

*2: For explosion proof types, specify type of explosion proof

certification using the optional codes. In case of the TIIS
flameproof type, the remote flowtube is available only for
combined use with the AXFA14. For the TIIS flameproof type
with wiring using a flameproof packing adapter, select optional
code G12 or G11. Available only for JIS G1/2 female electrical
connections.

*3: JIS G1/2 female electrical connection is available only for TIIS

flameproof type.

*4: In case of integral flowmeters of the TIIS flameproof type,

select “with indicator”(code 1 or 2).

*5: For F

OUNDATION

Fieldbus protocol, refer to IM 01E20F02-01E

*6: For PROFIBUS PA protocol, refer to IM 01E20F12-01E

AXFA14

Use (*2)

Output Signal and
Communication

Power Supply

Electrical Connections
(*3)

Indicator (*1)(*4)

Option

Advertising