12. EXPLOSION PROTECTED TYPE INSTRUMENT

• Apply a nonhardening sealant to the terminal box

connection port and to the threads on the flameproof
packing adapter for waterproofing.

• The same wiring as described below is required for

all of the terminal box connection ports except when
a four-wire cable is used for power input and signal
output with DC power supply.

Flameproof
packing adapter

Wiring metal
conduit

Flexible metal conduit

Tee

Drain plug

F0810.EPS

Apply a non-hardening
sealant to the threads
for waterproofing.

Figure 12.4.2 Typical Wiring Using Flexible Metal Conduit

Follow the procedure for flameproof packing adapter
setting. (refer to Figure 12.4.3)

CAUTION

Before fighting, confirm cable length from
terminal to flameproof packing adapter when
setting. Once it is tightened, loosening and re-
tightening may damage its sealing performance.

(a) Loosen the locking screw and remove the terminal

box cover.

(b) Measure the cable outer diameter in two directions

to within 0.1 mm.

(c) Calculate the average of the two diameters, and use

packing with an internal diameter nearest to this
value (see Table 12.4.1).

(d) Screw the flameproof packing adapter into the

terminal box until the O-ring touches the wiring
port (at least 6 full turns), and firmly tighten the
lock nut.

(e) Insert the cable through the union cover, the union

coupling, the clamp nut, the clamp ring, the gland,
the washer, the rubber packing, and the packing
box, in that order.

(f) Insert the end of the cable into the terminal box.
(g) Tighten the union cover to grip the cable. When

tightening the union cover, tighten approximately
one turn past the point where the cable will no
longer move up and down.

Proper tightening is important. If it is too tight, a
circuit break in the cable may occur; if not tight
enough, the flameproof effectiveness will be
compromised.

(h) Fasten the cable by tightening the clamp nut.
(i) Tighten the lock nut on the union cover.
(j) Connect the cable wires to each terminal.

F0811.EPS

Adapter body

Rubber packing

Washer

Packing box

Gland

Clamp ring

Clamp nut

Union coupling

Union cover

Wrench

O-ring

Lock nut

Wrench

Lock nut

Cable

Apply a non-
hardnening sealant to
the threads for
waterproofing.

Figure 12.4.3 Installing Flameproof Packing Adapter

(2-2) Cable Wiring Using Flameproof Metal

Conduit

• A seal fitting must be installed near the terminal box

connection port for a sealed construction.

• Apply a non-hardening sealant to the threads of the

terminal box connection port, flexible metal conduit
and seal fitting for waterproofing.

• The same wiring as described below is required for

all of the terminal box connection ports except when
a four-wire cable is used for power input and signal
output with DC power supply.

F0812.EPS

Non-hazardous
area

Hazardous area

Flameproof
heavy-gauge
steel conduit

Tee

Drain plug

Seal fitting

Gas sealing
device

Flameproof flrxible
metal conduit

After wrining, impregnate the
fitting with a compound to seal tubing.

Apply a non-hardening
sealant to the threads
of these fittings for
waterproofing

Figure 12.4.4 Typical Wiring Using Flameproof Metal

Conduit