2 zero adjustment via external status input, Zero adjustment via external status input -3 – Yokogawa AXFA14G/C User Manual

Page 95

Advertising
background image

IM 01E20C02-01E

9-3

9. ACTUAL OPERATION

Auto zero adjustment function is being executed
(about 30 seconds).

When zero adjustment function has been completed,
the system automatically returns to the sub-item
selection screen (D).

NOTE

The results of M10: Auto Zero Exe can be
displayed using M11: Magflow Zero. Alterna-
tively, if the results of the automatic zero
adjustment exceed the rated value, the warn-
ing 82: Auto Zero Wng will be displayed.

9.1.2

Zero Adjustment via External Status Input

This section describes the procedure for zero adjustment via external status input. (For
more details regarding external status input, refer to Chapter 6: Parameter Description.)

CAUTION

In certain cases where the multiple range function is being used with other status
inputs, it may not be possible to perform settings for automatic zero adjustment.
For more details, refer to the description of multiple ranges from Chapter 6:
Parameter Description.

In order to carry out zero adjustment via external status input, it will be necessary to set
“Ext Auto Zero (I)” using F21: DIO Function. The following describes the setting
procedure:

Once in Setting Mode, use the

switch to

move the cursor to F: Status Function.

Touch the

switch to access Sub-item

Parameter Search Mode.

Touch the

switch once to move the cursor to

F21: DIO Function.

The cursor has been moved to F21: DIO Function
in this screen. (Sub-item selection screen (E))

Touch the

switch to access Parameter

Replacement Mode.

Setting Mode

Major item

parameter

Setting Mode

E:Pulse Set

F:Status Function

G:Alarm

Major item

Sub-item

parameter

Major item

Sub-item

selection (E)

F:Status Function

41:Bi Direction Hys

20:DO Function

21:DIO Function

F:Status Function

20:DO Function

21:DIO Function

22:DO Active Mode

Sub-item

Parameter

Search Mode

Start:

Major Item

Parameter

Search Mode

M:Adjustment

10:Auto Zero Exe

11:Magflow Zero

Sub-item

Parameter

Search Mode

Major item

Sub-item

selection (D)

F0901.EPS

Now Auto Zero

Executing...

Advertising
This manual is related to the following products: