IM 01E20C02-01E

6-9

6. PARAMETER DESCRIPTION

(8) Item H (Menu H): Display Setting items

Menu H contains setting items that are relevant to display on the display unit.

T0609.EPS

Item

Name

Display unit

(BRAIN)

Data range

Display unit

/BRAIN

Default value

(*): Indicated item

Units

R/W

Position

of decimal

point

Description

Display Set
(DISP SET)

Display Select1
(DISP SELECT1)

Display Select2
(DISP SELECT2)

English
Japanese
French
German
Italian
Spanish

Language
(LANGUAGE)

Display Select3
(DISP SELECT3)

Display Cycle
(DISP CYCLE)

Flow Rate(%)
Flow Rate
Flow Rate(mA)
Forward Total
Reverse Total
Dif Total

English

Off
Flow Rate(%)
Flow Rate
Flow Rate(mA)
Flow Rate(Bar)
Forward Total
Reverse Total
Dif Total
Tag No
Adhesion Check
Communication

Same as H11
(Display Select2)

W

200ms
400ms
1s
2s
4s
8s

W

W

W

W

R

Good
Error

H11


(SELF CHECK)

H12

H20

H30

H60

Selects the display cycle.

Selects content of the third line
for Display Mode. Linked with
B42.

Selects content of the second line
for Display Mode. Linked with
B41.

400ms

See “6.5 Alarm Functions”.

Selects the language used by the
display unit. Linked with B10.

H10

Flow Rate(%)

Off

Off

Selects content of the first line
for Display Mode. Linked with
B40.

H00

(9) Item J (Menu J): Auxiliary Function Setting items

Menu J contains setting items such as the flow direction, rate limits, and low cut.

T0610-1.EPS

Item

Name

Display unit

(BRAIN)

Data range

Display unit

/BRAIN

Default value

(*): Indicated item

Units

R/W

Position

of decimal

point

Description

1

0

s

0

0

1

Flow Direction
(FLOW DIRECT)

4-20mA High Lmt
(4-20 HI LMT)

Rate Limit
(RATE LIMIT)

4-20mA Low Lmt
(4-20 LOW LMT)

Dead Time
(DEAD TIME)

Aux
(AUX)

4-20mA Low Cut
(4-20 LOW CUT)

%

0 to10

%

%

-20.0 to 100.0

Forward
Reverse

0.0 to 120.0

W

W

W

0 to 15

W

0 to 10

%

W

W

0s

Damping
No Damping

T/P Damp Select
(T/P DAMP SEL)

W

J22

J21

J20

J24

Pulsing Flow
(PULSING FLOW)

Damping

Sets the high limit for current
output

Selects the flow direction.

Sets the low limit for current
output

Sets the level to reduce output
fluctuation.

Sets the dead time to reduce output
fluctuation. When “0” is set, rate
limit function is not available.

Selects whether the flow rate value
obtained through damping calculation
for total/pulse or the instantaneous
flow rate value (no damping) for total/
pulse is to be used.

Selects whether pulsing flow is to
be supported.

J23

5%

No

Forward

120.0%

W

No
Yes

0%

J10

J00

J11

-20.0%

J12

Sets the range in vicinity of 0%
within which the current output will
be 4 mA.