Terminal configuration, Terminal wiring – Yokogawa AXFA14G/C User Manual

Page 107

Advertising
background image

IM 01E20C02-01E

11-5

11. OUTLINE

Signal Cable:

Model

Suffix Code

Description

AXFC

Termination

Cable Length

Option

Magnetic Flowmeter
Dedicated Signal cable for the ADMAG AXF series

No Termination.

A set of termination parts for M4 screws is attached.
Terminated for the AXFA11/14 Remote Converter.

Designate the cable length, unit: m
Following “L”, specify the cable in three digits as
multiple of 1 meter (e.g., 001, 002, or 005) for a
length up to 5 m, or as a multiple of 5 meters
(i.e., 005, 010, 015, or the like).
The maximum cable length:
200 m for combined use with AXFA11
100 m for combined use with AXFA14

With termination parts sets.
Following “C”, specify the q’ty of sets of
termination parts in one digits.

· · · · · · · · · · · · ·

-0 · · · · · · · · · · ·

-4 · · · · · · · · · · ·

-L

ٗٗٗ · · · · ·

/C

ٗ

T04.EPS

Note:
• The cable is constructed with double shielding over the two

conductors, and uses heat-resistant vinyl as the outer covering

material.

Finished diameture: 10.5 mm (0.41 in.)
Maximum temperature: +80˚C (+175˚F)

• Unnecessary to order the above cable for submersible type

flowtube or for the optional code DHC flowtube because the
flowtube is wired with 30 m (98 ft) cable.

• For excitation cable, prepare a two-core cable at the customer side.

Terminal Configuration “

SB

B

A

SA

C

EX2

EX1

DIO-

DIO+

DO-

DO+

I-

I+

L/+

N/-

F05.EPS

Terminal Wiring “

T06.EPS

Flow singal
input

Excitation current
Output

Power supply

Current output
4 to 20mA DC

Pulse output/
Alarm output/
Status output

Alarm output/
Status output/
Status input

Functional grounding

Terminal
Symbols

Description

EX1
EX2

C

SA

A
B

SB

Terminal
Symbols

Description

N/–

L/+

I+
I–

DO+
DO–

DIO+
DIO–

Protective grounding
(Outside of the terminal)