8 installing the cover, Installing the cover -8, Status input – Yokogawa AXFA14G/C User Manual

Page 20

Advertising
background image

IM 01E20C02-01E

4-8

4. WIRING

F0417.EPS

Protective diode

PULSE OUT

PULSE OUT

AXFA14

AXFA14

DO+

DO-

DO+

DO-

Output voltage: 24 V DC

Ϯ20%

• Current: 150 mA or less
Pulse rate: 0.0001 to 2 pps
Pulse width: 20, 33, 50, 100 ms

Mechanical Counter

Electronic Counter

Load

Figure 4.4.9

Active Pulse Output Connection (Optional
code EM)

Status Input

IMPORTANT

Status inputs are designed for use with no-
voltage (dry) contacts. Be careful not to connect
the status to any signal source carrying voltage.
Applying voltage may damage the input circuit.

AXFA14

DIO+

DIO-

F0418.EPS

No-voltage status input

Closed: Less than 200

Open:

More than 100 k

Figure 4.4.10 Status Input Connection

NOTE

For status input to the DIO terminals, parameters
must be set. Refer to “Chapter 6: Parameter
Description” in this manual.

Status Output / Alarm Output

IMPORTANT

Since this is an isolated transistor output, be
careful of voltage and polarity when wiring. Do
not apply a voltage larger than 30V DC or a
current larger than 0.2A in order to prevent
damage to the instrument.

This output cannot switch an AC load. To switch
an AC load, an intermediate relay must be
inserted as shown in Figure 4.4.11.
*The alarm output operates from open (normal)
to closed (alarm occurrence) in the default value
(as setup upon plant shipment). Changes can
be made via the parameter settings.

F0419.EPS

Load

Protective diode

External power supply
30V DC, 0.2A. max

AXFA14

AXFA14

This connection is not possible.

DO+ (or DIO+)

DO- (or DIO-)

DO+ (or DIO+)

DO- (or DIO-)

Electromagnetic

valve

AC power supply

Relay

Figure 4.4.11 Status Output/Alarm Output Connection

NOTE

For status and alarm outputs from the DO or
DIO terminals, parameters must be set. Refer to
“Chapter 6: Parameter Description” in this
manual.

4.4.8

Installing the Cover

Install the cover to the flowmeter by turning it in the
direction of the arrow as shown below. Tighten cover
locking screw 2 counterclockwise using a hexagonal
wrench (nominal size 3 mm) to lock the cover.

F0420.EPS

Cover locking
screws

Figure 4.4.12 Installing the Terminal Box Cover