4 rs-422/485 connection procedure, Rs-422/485 connection procedure -6, Connection • connecting the cable – Yokogawa Touch Screen GP20 User Manual

Page 12: Signal names, Connecting to the host device, Connection example to the host device

Advertising
background image

1-6

IM 04L51B01-17EN

1.2.4

RS-422/485 Connection Procedure

Connect a cable to the terminal.

Connection

• Connecting the Cable

As shown in the figure below, remove approximately 6 mm of the covering from the end of

the cable to expose the conductor. Keep the exposed section from the end of the shield

within 5 cm.

Two-wire system

Four-wire system

FG SG SDB+ SDA– RDB+ RDA–

FG SG SDB+ SDA– RDB+ RDA–

Electric potential

of the shield

Shield

FG SDB+

SG SDA−

Electric potential

of the shield

Shield

FG SDB+

SG SDA−

RDB+

RDA−

Recommended torque

for tightening the screw: 0.2 N•m

• Signal names

Each terminal corresponds to the signal indicated below.

Signal Name

Meaning

FG

Frame ground of the GX/GP.

SG

Signal ground.

SDB+

Send data B (+).

SDA–

Send data A (–).

RDB+

Receive data B (+).

RDA–

Receive data A (–).

Connecting to the host device

The figure below illustrates the connection of the GX/GP to a host device. If the port on the

host device is an RS-232 interface, connect a converter.

RS-422/485

terminal on the GX/GP

Host computer

or host device

Host device side

Converter

RS-422/485

RS-422/485

terminal on the GX/GP

Host computer

RS-232

RS-422/485

Host device side

Connection example to the host device

A connection can be made with a host device having a RS-232, RS422, or RS-485 port. In

the case of RS-232, a converter is used. See the connection examples below for a typical

converter terminal. For details, see the manual that comes with the converter.

RS-422/485 Port

Converter

SDA(–)

TD(–)

SDB(+)

TD(+)

RDA(–)

RD(–)

RDB(+)

RD(+)

SG

SHIELD

FG

EARTH

There is no problem of connecting a 220-Ω terminator at either end if YOKOGAWA’s PLCs

or temperature controllers are also connected to the communication line.