p7 Lower limit of the color scale band display
(span lower limit to span upper limit)
Query
SBandIO[,p1]?
Example For channel 0001, set a blue band in the range
of -0.5000 to 1.0000.
SBandIO,0001,In,0,0,255,5000,10000
Description
• You cannot set this on a “Skip” channel. p2 is fixed to
Off.
• If p2=Off, you cannot set p3 or subsequent
parameters.
• For details on RGB values, see “Description” of the
SAlmMarkIO
Alarm Mark
Sets the display of the marker that indicates the specified
alarm position of an AI or DI channel.
Syntax SAlmMarkIO,p1,p2,p3,p4,p5,p6,p7,p8
,p9,p10,p11,p12,p13,p14,p15
p1 Channel number
p2 Whether to display the alarm mark on the
scale (Off, On)
p3 Alarm mark type
Alarm Display the default alarm mark
Fixed Display the mark with the
specified color
P4 R value of the RGB mark colors for alarm
1 ( 0 to 255)
p5 G value of the RGB mark colors for alarm
1 ( 0 to 255)
p6 B value of the RGB mark colors for alarm
1 ( 0 to 255)
p7 R value of the RGB mark colors for alarm
2 ( 0 to 255)
p8 G value of the RGB mark colors for alarm
2 ( 0 to 255)
p9 B value of the RGB mark colors for alarm
2 ( 0 to 255)
p10 R value of the RGB mark colors for alarm
3 ( 0 to 255)
p11 G value of the RGB mark colors for alarm
3 ( 0 to 255)
p12 B value of the RGB mark colors for alarm
3 ( 0 to 255)
p13 R value of the RGB mark colors for alarm
4 ( 0 to 255)
p14 G value of the RGB mark colors for alarm
4 ( 0 to 255)
p15 B value of the RGB mark colors for alarm
4 ( 0 to 255)
Query
SAlmMarkIO[,p1]?
Example Display the alarm marks for alarms 1 to 4
of channel 0001 in fixed colors red, brown,
orange, and yellow, respectively.
SAlmMarkIO,0001,On,Fixed,255,0,0,
165,42,42,255,165,0,255,255,0
Description
• For details on RGB values, see “Description” of the
SValueIO
Upper/Lower Limit Display Characters
Sets the upper/lower limit display characters of DI channel
or DO channel.
Syntax SValueIO,p1,p2,p3
p1 Channel number
p2 Lower limit display string (up to 8
characters, UTF-8)
p3 Upper limit display string (up to 8
characters, UTF-8)
Query
SValueIO[,p1]?
Example For channel 0001, set the lower limit to “OFF”
and the upper limit to “ON.”
SValueIO,0001,’OFF’,’ON’
SCalibIO
Calibration Correction
Sets the calibration correction for AI channels.
Disable Calibration Correction
Syntax SCalibIO,p1,p2
p1 Channel number
p2 Linearizer mode (Off)
Use Calibration Correction
Syntax SCalibIO,p1
p1 Channel number
p2 Linearizer mode
Appro Linearizer approximation
Bias
Linearizer bias
p3 Number of set points (2 to 12)
P4 Input value of set point 1
p5 Output value of set point 1
p6 Input value of set point 2
p7 Output value of set point 2
p8 Input value of set point 3
p9 Output value of set point 3
p10 Input value of set point 4
p11 Output value of set point 4
p12 Input value of set point 5
p13 Output value of set point 5
p14 Input value of set point 6
p15 Output value of set point 6
p16 Input value of set point 7
p17 Output value of set point 7
p18 Input value of set point 8
p19 Output value of set point 8
p20 Input value of set point 9
p21 Output value of set point 9
p22 Input value of set point 10
p23 Output value of set point 10
p24 Input value of set point 11
p25 Output value of set point 11
p26 Input value of set point 12
p27 Output value of set point 12
Query
SCalibIO[,p1]?
2.4 Setting Commands