12 app, Srangeai measurement range of ai channel – Yokogawa Touch Screen GP20 User Manual

Page 27

Advertising
background image

2-13

IM 04L51B01-17EN

Commands and Responses

1

2

App

SRangeAI

Measurement Range of AI Channel

Sets the measurement range of an AI channel.

Unused Channels

Syntax SRangeAI,p1,p2

p1 Channel number

p2 Input type (Skip)

Channels Whose Input Type Is DI and No Math
Syntax
SRangeAI,p1,p2,p3,p4,p5,p6

p1 Channel number

p2 Input type (DI)

p3 Range (see “Description.”)

P4 Calculation type (Off)

p5 Span lower limit

p6 Span upper limit

Channels Whose Input Type Is Volt, TC, or RTD and

No Calculation

Syntax SRangeAI,p1,p2,p3,p4,p5,p6,p7

p1 Channel number

p2 Input type (Volt, TC, RTD)

p3 Range (see “Description.”)

P4 Calculation type (Off)

p5 Span lower limit

p6 Span upper limit

p7 Bias (–999999 to 999999)

Delta Channels
Syntax
SRangeAI,p1,p2,p3,p4,p5,p6,p7,p8

p1 Channel number

p2 Input type (Volt, TC, RTD, DI)

p3 Range (see “Description.”)

P4 Calculation type (Delta)

p5 Span lower limit

p6 Span upper limit

p7 Bias (–999999 to 999999) (can be set

when p2 is not set to DI)

p8 Reference channel number

Scaling Channels
Syntax
SRangeAI,p1,p2,p3,p4,p5,p6,p7,p8,p

9,p10,p11

p1 Channel number

p2 Input type (Volt, TC, RTD, DI)

p3 Range (see “Description.”)

P4 Calculation type (Scale)

p5 Span lower limit

p6 Span upper limit

p7 Bias (–999999 to 999999) (can be set

when p2 is not set to DI)

p8 Decimal Place (0 to 5)

p9 Scaling lower limit

p10 Scaling upper limit

p11 Unit (up to 6 characters, UTF-8)

Unified Signal Input Channels (Input Type Is GS)
Syntax
SRangeAI,p1,p2,p3,p4,p5,p6,p7,p8,p

9,p10,p11,p12,p13

p1 Channel number

p2 Input type (GS)

p3 Range (see “Description.”)

P4 Calculation type (Scale)

p5 Span lower limit

p6 Span upper limit

p7 Bias (–999999 to 999999)

p8 Decimal Place (0 to 5)

p9 Scaling lower limit

p10 Scaling upper limit

p11 Unit (up to 6 characters, UTF-8)

p12 Low-cut function (Off, On)

p13 Low-cut output (Zero, Linear)

Square Root Channels
Syntax
SRangeAI,p1,p2,p3,p4,p5,p6,p7,p8,p

9,p10,p11,p12,p13,p14

p1 Channel number

p2 Input type (Volt, GS)

p3 Range (see “Description.”)

P4 Calculation type (Sqrt)

p5 Span lower limit

p6 Span upper limit

p7 Bias (–999999 to 999999)

p8 Decimal Place (0 to 5)

p9 Scaling lower limit

p10 Scaling upper limit

p11 Unit (up to 6 characters, UTF-8)

p12 Low-cut function (Off, On)

p13 Low-cut output (Zero, Linear)

p14 Low-cut point (0 to 50)

Query

SRangeAI[,p1]?

Example Measure -0.5000 to 1.0000 V on channel 0002.

No scaling. No bias.

SRangeAI,0002,Volt,2V,Off,–5000,

10000,0

Description

• You cannot use this command to configure settings

while recording is in progress.

• You cannot use this command to configure settings

while computation is in progress.

• If p2=TC/RTD/DI, you cannot specify p4=Sqrt.

• If p2=GS, you cannot specify p4=Off/Delta.

• If p2=DI, you cannot set p7.

• RTD cannot be specified if an electromagnetic relay

scanner type (Type suffix code: -T1) analog input

module is in use.

• The settable items for p3 are shown below.

2.4 Setting Commands

Advertising
This manual is related to the following products: