Smultipattern multi panel division, Smultikind multi panel – Yokogawa Touch Screen GP20 User Manual
Page 56

2-42
IM 04L51B01-17EN
p1 Information type (see the table below)
p2 Status (see the table below)
Information Type
Status
p1
Description
p2
Digital
Digital value display
Off, On
Scroll
Auto scroll
Off, On
Message
Message display
Stream, List
Trend
All channel/group display
Group, All
Axis
Time axis on historical
trend
1, 2, 3, 4, 5,
6, 7, 8
Value
Digital value display on
historical trend
4Value, Max,
Min
Data
Historical data type
Disp, Event1
DigitalWave
Digital waveform display
Off, On
Alarm
Alarm display
Watch, List
Alarm_Sort
Alarm sort item
Time, Channel,
Level, Type
Alarm_Order
Alarm sort order
Ascending,
Descending
Message_Sort Message sort item
Datatime,
WriteTime,
Message,
Group, User
Message_
Order
Message sort order
Ascending,
Descending
Memory_Data
Memory data type
Disp, Event1
Overview
Overview display
Grouping, All
Multi_No
Multi panel number
1 to 20
DigitalPos
Digital display position
Default, Top,
Bottom, Left,
Right
DigitalLabel Display string display
Off, On
Modbus_M
Modbus master status
display type
Overview, List
Modbus_C
Modbus client status
display type
Overview, List
Query
SMonitor[,p1]?
Example Set the trend display to all-channel display.
SMonitor,Trend,All
Description
• Modbus_M and Modbus_C are an option (/MC).
SMultiPattern
Multi Panel Division
Sets the multi panel multi panel pattern.
Syntax SMultiPattern,p1,p2,p3
p1 Registration number (1 to 20)
p2 Multi panel pattern
Wide2
Split 2 Wide
Tall2
Split 2 Tall
Wide3
Split 3 Wide
Tall3
Split 3 Tall
Split4
Split 4 Even
Even5
Split 5 Even
Odd5
Split 5 Odd
Even6
Split 6 Even
Odd6
Split 6 Odd
p3 Multi panel name (up to 16 characters,
UTF-8)
Query
SMultiPattern[,p1]?
Example Set the panel of registration number 1 to
“Split 2 Wide.” Set the multi panel name to
“Monitor1.”
SMultiPattern,1,Wide2,’Monitor1’
Description
• This command is only valid for the GX20/GP20.
SMultiKind
Multi Panel
Set the screens to display on the multi panel.
Syntax SMultiKind,p1,p2,p3,p4
p1 Registration number (1 to 20)
p2 Screen position (1 to 6)
p3 Screen type
Trend
Trend
Digital
Digital
Bar
Bar graph
Overview OVERVIEW
Alarm
Alarm summary
Message
Message summary
Memory
Memory summary
Report
Report summary
Modbus-M Modbus master status
Mosbus-C Modbus client status
Action-
Log
Event log
Error-Log Error log
Commu-Log Communication log
Ftp-Log
FTP log
Web-Log
Web log
Mail-Log Mail log
Modbus-
Log
Modbus log
Sntp-Log SNTP log
Dhcp-Log DHCP log
Network
Network information
P4 Display group number
Query
SMultiKind[,p1[,p2]]?
Example Display the bar graph of display group 8 in
screen position 3 of the registration number 1
panel.
SMultiKind,1,3,Bar,8
Description
• This command is only valid for the GX20/GP20.
• Report is an option (/MT).
• Modbus-M and Modbus-C are an option (/MC).
SHomeMonitor
Standard Screen Information
Sets the standard screen display information.
Syntax SHomeMonitor,p1,p2
p1 Information type (see the table of the
2.4 Setting Commands