Smultipattern multi panel division, Smultikind multi panel – Yokogawa Touch Screen GP20 User Manual

Page 56

Advertising
background image

2-42

IM 04L51B01-17EN

p1 Information type (see the table below)

p2 Status (see the table below)

Information Type

Status

p1

Description

p2

Digital

Digital value display

Off, On

Scroll

Auto scroll

Off, On

Message

Message display

Stream, List

Trend

All channel/group display

Group, All

Axis

Time axis on historical

trend

1, 2, 3, 4, 5,

6, 7, 8

Value

Digital value display on

historical trend

4Value, Max,

Min

Data

Historical data type

Disp, Event1

DigitalWave

Digital waveform display

Off, On

Alarm

Alarm display

Watch, List

Alarm_Sort

Alarm sort item

Time, Channel,

Level, Type

Alarm_Order

Alarm sort order

Ascending,

Descending

Message_Sort Message sort item

Datatime,

WriteTime,

Message,

Group, User

Message_

Order

Message sort order

Ascending,

Descending

Memory_Data

Memory data type

Disp, Event1

Overview

Overview display

Grouping, All

Multi_No

Multi panel number

1 to 20

DigitalPos

Digital display position

Default, Top,

Bottom, Left,

Right

DigitalLabel Display string display

Off, On

Modbus_M

Modbus master status

display type

Overview, List

Modbus_C

Modbus client status

display type

Overview, List

Query

SMonitor[,p1]?

Example Set the trend display to all-channel display.

SMonitor,Trend,All

Description
• Modbus_M and Modbus_C are an option (/MC).

SMultiPattern

Multi Panel Division

Sets the multi panel multi panel pattern.

Syntax SMultiPattern,p1,p2,p3

p1 Registration number (1 to 20)

p2 Multi panel pattern

Wide2

Split 2 Wide

Tall2

Split 2 Tall

Wide3

Split 3 Wide

Tall3

Split 3 Tall

Split4

Split 4 Even

Even5

Split 5 Even

Odd5

Split 5 Odd

Even6

Split 6 Even

Odd6

Split 6 Odd

p3 Multi panel name (up to 16 characters,

UTF-8)

Query

SMultiPattern[,p1]?

Example Set the panel of registration number 1 to

“Split 2 Wide.” Set the multi panel name to

“Monitor1.”

SMultiPattern,1,Wide2,’Monitor1’

Description
• This command is only valid for the GX20/GP20.

SMultiKind

Multi Panel

Set the screens to display on the multi panel.

Syntax SMultiKind,p1,p2,p3,p4

p1 Registration number (1 to 20)

p2 Screen position (1 to 6)

p3 Screen type

Trend

Trend

Digital

Digital

Bar

Bar graph

Overview OVERVIEW

Alarm

Alarm summary

Message

Message summary

Memory

Memory summary

Report

Report summary

Modbus-M Modbus master status

Mosbus-C Modbus client status

Action-

Log

Event log

Error-Log Error log

Commu-Log Communication log

Ftp-Log

FTP log

Web-Log

Web log

Mail-Log Mail log

Modbus-

Log

Modbus log

Sntp-Log SNTP log

Dhcp-Log DHCP log

Network

Network information

P4 Display group number

Query

SMultiKind[,p1[,p2]]?

Example Display the bar graph of display group 8 in

screen position 3 of the registration number 1

panel.

SMultiKind,1,3,Bar,8

Description
• This command is only valid for the GX20/GP20.
• Report is an option (/MT).
• Modbus-M and Modbus-C are an option (/MC).

SHomeMonitor

Standard Screen Information

Sets the standard screen display information.

Syntax SHomeMonitor,p1,p2

p1 Information type (see the table of the

SMonitor

command)

2.4 Setting Commands

Advertising
This manual is related to the following products: