12 app, Srangecom measurement range (/mc), Svaluecom preset operation (/mc) – Yokogawa Touch Screen GP20 User Manual

Page 37: Swdcom watchdog timer (/mc)

Advertising
background image

2-23

IM 04L51B01-17EN

Commands and Responses

1

2

App

SAlmMarkMath,015,On,Fixed,255,0,0,

165,42,42,255,165,0,255,255,0

Description

For details on RGB values, see “Description” of the

SColorIO

command.

SRangeCom

Measurement Range (/MC)

Sets the measurement range of a communication

channel.

Unused Channels

Syntax SRangeCom,p1,p2

p1 Channel number

p2 Enable or disable (Off)

Used Channels
Syntax
SRangeCom,p1,p2,p3,p4,p5,p6

p1 Channel number

p2 Enable or disable (On)

p3 Decimal Place (0 to 5)

P4 Span lower limit (-9999999 to 99999999)

p5 Span upper limit (-9999999 to 99999999)

p6 Unit (up to 6 characters, UTF-8)

Query

SRangeCom[,p1]?

Example Measure 0.00 to 100.00% on communication

channel 025.

SRangeCom,025,On,2,0,10000,’%’

Description

• You cannot use this command to configure settings

while recording is in progress.

• You cannot use this command to configure settings

while computation is in progress.

• If p2=Off, you cannot set p3 or subsequent

parameters.

• You cannot set the span upper and lower limits to the

same value.

SValueCom

Preset Operation (/MC)

Sets the preset operation of a communication channel.

Syntax

SValueCom,p1,p2,p3

p1 Channel number

p2 Value at power-on (Preset, Last)

p3 Preset value (–9.999999E+29 to –1E–30,

0, 1E–30 to 9.999999E+29)

Query

SValueCom[,p1]?

Example At power-on, replace the communication

channel 025 value with the preset value of 0.5.

SValueCom,025,Preset,0.5

SWDCom

Watchdog Timer (/MC)

Sets the watchdog timer of a communication channel.

Channels That Do Not Use Watchdog Timers

Syntax SWDCom,p1,p2

p1 Channel number

p2 Watchdog timer usage (Off)

Channels That Use Watchdog Timers
Syntax
SWDCom,p1,p2,p3,p4

p1 Channel number

p2 Watchdog timer usage (On)

2.4 Setting Commands

Advertising
This manual is related to the following products: