Destination and behavior for each, Mail header (recipient address), Smail destination and behavior for each mail type – Yokogawa Touch Screen GP20 User Manual

Page 52: Smailalarm alarm notification mail target channels, Smailtime scheduled transmission times

Advertising
background image

2-38

IM 04L51B01-17EN

Mail Header (Recipient Address)

Sets the mail header including the recipient address.

Syntax SMailHead,p1,p2,p3,p4

p1 Sender address (up to 64 characters,

ASCII)

p2 Recipient address 1 (up to 150

characters, ASCII)

p3 Recipient address 2 (up to 150

characters, ASCII)

P4 Character string to add to the subject (up

to 32 characters, ASCII)

Query

SMailHead?

Example Set the sender address to “recorder1@data.

com” and the recipient address to “pc1@data.

com.” Add “part1” to the subject.

SMailHead,’[email protected]’,

[email protected]’,,’part1’

SMailBasic

Common Section of the Mail Body

Sets the items that are common to the body of all mails.

Syntax SMailBasic,p1,p2

p1 Header string (up to 128 characters, UTF-

8)

p2 Include source URL (Off, On)

Query

SMailBasic?

Example Set the header to “recorder1,” and include the

source URL.

SMailBasic,’recorder1’,On

SMail

Destination and Behavior for Each Mail

Type

Sets the destination and behavior for each mail type.

Alarm Notification

Syntax SMail,p1,p2,p3,p4,p5,p6

p1 Setting type (Alarm)

p2 Recipient (Off, 1, 2, 1+2)

Off

Not send

1

Send to recipient 1

2

Send to recipient 1

1+2

Send to recipient 1 and 2

p3 Inclusion of instantaneous data (Off, On)

P4 Alarm action

On

Send mails when alarms occur

On+Off Send mails when alarms occur

and when they are cleared

p5 Inclusion of tag number or channel

number in subject (Off, On)

Scheduled Transmission

Syntax SMail,p1,p2,p3

p1 Setting type (Time)

p2 Recipient (Off, 1, 2, 1+2)

p3 Inclusion of instantaneous data (Off, On)

Report Notification

Syntax SMail,p1,p2

p1 Setting type (Report)

p2 Recipient (Off, 1, 2, 1+2)

Media Alarm Notification

Syntax SMail,p1,p2

p1 Setting type (Media)

p2 Recipient (Off, 1, 2, 1+2)

Power failure notification

Syntax SMail,p1,p2

p1 Setting type (Power)

p2 Recipient (Off, 1, 2, 1+2)

System Error Notification

Syntax SMail,p1,p2

p1 Setting type (System)

p2 Recipient (Off, 1, 2, 1+2)

Query

SMail[p1]?

Example Send alarm notifications to recipient 1 when

alarms occur and when they are cleared.

Include instantaneous data at the time of

transmission, and include the tag number or

channel number in the subject.

SMail,Alarm,1,On,On+Off,On

Description
The report function is an option (/MT).

SMailAlarm

Alarm Notification Mail Target Channels

Detects the alarm status of the specified channels and

sends alarm notifications.

Syntax SMailAlarm,p1

p1 Channel string (up to 249 characters, up

to 50 channels)

• Use channel number to specify the

channels. 4-digit numbers for I/O

channels. Numbers that start with “A”

for math channels (A015). Numbers

that start with “C” for communication

channels (C020). The maximum

number of characters per channel is 4.

• Use periods to separate channel

numbers (see example).

• To specify all channels from the first

channel to the last channel, delimit the

channels with a hyphen. An error will

occur if there are no valid channels in

the hyphen designated channels.

Query

SMailAlarm?

The channel string is output exactly as it is

specified.

Example Set the target channels to channels 0001 to

0021, 0101, A025, and C003.

SMailAlarm,’1-21.101.A25.C3’

SMailTime

Scheduled Transmission Times

Sets the scheduled transmission times.

Syntax SMailTime,p1,p2,p3,p4

p1 Recipient (1 or 2)

p2 Reference time: Hours (HH) (00 to 23)

2.4 Setting Commands