Sfailsts instrument status to output (/fl), Sprinter printer, Sled led indicator operation – Yokogawa Touch Screen GP20 User Manual

Page 48: Ssound sound, Sinstrutag instruments tag, Sconfcmt setting file comment, Susbinput usb input device, Sswitch internal switch operation

Advertising
background image

2-34

IM 04L51B01-17EN

You cannot use this command to configure settings

while computation is in progress.

SFailSts

Instrument Status to Output (/FL)

Sets the instrument status to output from the fail relay (DO

channel).

Syntax SFailSts,p1,p2,p3,p4,p5

p1 Memory/media status (Off, On)

p2 Measurement error (Off, On)

p3 Communication error (Off, On)

P4 Recording stop (Off, On)

p5 Alarm (Off, On)

Query

SFailSts?

Example Output all information.

SFailSts,On,On,On,On,On

Description
You cannot use this command to configure settings

while recording is in progress.

You cannot use this command to configure settings

while computation is in progress.

SPrinter

Printer

Sets the printer.

Syntax SPrinter,p1,p2,p3,p4,p5,p6

p1 IP address (0. 0. 0. 0 to 255. 255. 255.

255)

p2 Paper size (A4, A3, Letter)

p3 Paper orientation (Horizontal, Vertical)

P4 Resolution [dpi] (300, 600)

p5 Number of copies (1 to 10)

p6 Snapshot (Off, On)

Query

SPrinter?

Example Set the IP address to “192.168.111.24,” the

paper size to A3, the paper orientation to

horizontal, the resolution to 600, the number of

copies to 2, and snapshot to On.

Sprinter,192.168.111.24,A3,Horizon

tal,600,2,On

SLed

LED Indicator Operation

Sets the operation of the LED indicators on the front

panel.

Syntax SLed,p,p2

p1 Type (Function)

p2 Operation

Off

Power state

AlarmAll Alarm

Query

SLed?

Example Set the LED indicator operation to “Alarm.”

SLed,Function,AlarmAll

SSound

Sound

Sets touch and warning sounds.

Syntax SSound,p1,p2

p1 Touch sound (Off, On)

p2 Warning sound (Off, On)

Query

SSound?

Example Enable touch and warning sounds.

SSound,On,On

SInstruTag

Instruments Tag

Sets tags.

Syntax SInstruTag,p1,p2

p1 Tag (up to 32 characters, UTF-8)

p2 Tag number (up to 16 characters, ASCII)

Query

SInstruTag?

Example Set the tag to assign to the GX/GP to “GX” and

the tag number to “12345.”

SinstruTag,’GX’,’12345’

SConfCmt

Setting File Comment

Sets the setting file comment.

Syntax SConfCmt,p1

p1 Setting file comment (up to 50 characters,

UTF-8)

Query

SConfCmt?

Example Set “SETTING FILE COMMENT.”

SConfCmt,’SETTING FILE COMMENT’

SUsbInput

USB Input Device

Specifies the USB input device.

Syntax

SUsbInput,p1

p1 USB input device type

Japanese_109 Japanese keyboard
English_104 English keyboard

Query

SUsbInput?

Example Specify the English keyboard.

SUsbInput,English_104

SSwitch

Internal Switch Operation

Sets the internal switch operation.

Syntax SSwitch,p1,p2,p3

p1 Internal switch number (1 to 100)

2.4 Setting Commands

Advertising
This manual is related to the following products: