4 users who are currently logged in (fuser), 4 users who are currently logged in (fuser) -60, Ascii output format, see – Yokogawa Touch Screen GP20 User Manual
Page 74
Advertising

2-60
IM 04L51B01-17EN
2.10.4 Users Who Are Currently Logged In (FUser)
The output in response to the command “FUser,0” is shown below.
Syntax
EA<crlf>
p_l_uuuuuuuuuuuuuuuuuuuu_abcdefghijk<crlf>
EN<crlf>
p
Login mode
M
Via general communication
W
Via Web (HTTP server)
F
Via FTP server
S
RS-232 or RS-422/485
D
Via front panel
l
User level
A
Administrator
U
User
uuuuuuuuuuuuuuuuuuuu
User name (fixed to 20 characters. Unused character
positions are filled with spaces.)
abcdefghijk
Authority of user
F
Free
L
Lock
a through k represent actions.
a
Memory
b
Math
c
Data save
d
Message
e
Batch
f
Alarm ACK
g
Communication
h
Touch operation
i
Time set
j
Setting operation
k
External media
2.10 ASCII Output Format