IM 04L51B01-17EN

OPassword

Changes the Password

Changes the password.

Syntax OPassword,p1,p2,p3

p1 Old password (up to 20 characters, ASCII)

p2 New password (up to 20 characters,

ASCII)

p3 New password (enter the same password

as p2)

Example Change the password from “PASS001” to

“WORD005.”

OPassword,’PASS001’,’WORD005’,’WO

RD005’

Description
For the characters that you can use for the password,

see

Appendix 1

.

OMath

Starts, Stops, or Resets Computation or

Clears the Computation Dropout Status

Display

Starts or stops computation, resets computed values, or

clears the computation dropout status display.

Syntax OMath,p1

p1 Action type (0)

0

Start computation

1

Stop computation

2

Reset computation

3

Clear the computation dropout status

display

Query

OMath?

Example Start computation.

OMath,0

Description
You cannot use this command while the GX/GP is

saving or loading setup data.

OSaveConf

Saves Setting Data

Saves the GX/GP setting data to the GX/GP external

storage medium.

Syntax OSaveConf,p1,p2,p3

p1 File name (up to 240 characters, ASCII)

Specify the path and file name, excluding

the extension.

p2 Medium

SD

SD memory card

USB

USB flash memory

p3 Setting file comment (up to 50 characters,

UTF-8)

Example Save setting data to a file named “SETFILE1”

to the SD memory card.

OSaveConf,SD,’SETFILE1’

Description
If you omit p3, the default setting file comment will be

added. You can edit the default setting file comment

from the GX/GP front panel.

OCommCh

Sets a Communication Channel to a

value

Sets a communication channel to a value.

Syntax OCommCh,p1,p2

p1 Communication channel

p2 Value

The setting range is as follows:

–9.9999999E+29 to –1.0000000E–30, 0,

1.0000000E-30 to 9.9999999E+29

The number of significant digits is 8.

Query

OCommCh[,p1]?

Example Set communication channel C001 to 2.5350.

OCommCh,C001,2.5350

OEMail

Starts or Stops the E-mail Transmission

Function

Starts or stops the e-mail transmission function.

Syntax OEMail,p1

p1 Action type

0 Start the e-mail transmission function.

1 Stop the e-mail transmission function.

Example Start the e-mail transmission function.

OEMail,0

OMBRestore

Recovers Modbus manually

Resumes command transmission from Modbus client or

Modbus master to devices in which communication errors

have occurred.

Syntax OMBRestore,p1

p1 Action type

0 Modbus client (Ethernet)

1 Modbus master (serial)

Example Manually recover the Modbus client.

OMBRestore,0

ORTReset

Resets a Relative Timer

Resets a relative timer.

Syntax ORTReset,p1

p1 Timer type

0

All timers

1 to 4 Timer number

Example Reset relative timer 2.

2.6 Operation Commands