Section 3 Preparation for measurement

Section

3


3-2 Voltage test leads and Clamp sensor connection

Ɣ Check the following before connection.

DANGER

Ɣ Use the Voltage test leads supplied with this instrument.
Ɣ Use the dedicated clamp sensor for this instrument, and confirm that the measured
current rating of the clamp sensor is not exceeded.
Ɣ Do not connect all the Voltage test leads or Clamp sensors unless required for
measuring the parameters desired.
Ɣ Connect the test leads and sensors to the instrument first, and only then connect
them to the circuit under test.
Ɣ Never disconnect the voltage test leads and sensors whilst the instrument is in use.

WARNING

Ɣ Confirm that the Function switch on the instrument is in the OFF position, and then

connect the test leads and sensors.

Ɣ Connect the test leads and sensors firmly to the instrument first.
Ɣ Never attempt to make any measurement if any abnormal conditions are noted,

such as a broken cover and exposed metal parts.

Ɣ Voltage test leads and clamp sensor connection

Follow the procedure below, and connect the Voltage test leads and Clamp
sensors.
(1) Confirm that the Function switch on the instrument is in the OFF

position.

(2) Connect the appropriate Voltage test leads to the Voltage input terminal

on the instrument.

(3) Connect the appropriate Clamp sensors to the Current input terminal on

the instrument.

* Match the direction of arrow marks indicated on the output terminal of the
clamp sensor and the mark on the Current input terminal on the instrument.