Essential Requirements for CE Compliance

The following conditions must be satisfied for MD60 drives to meet
the requirements of EN61800-3.

Grounding as described in figure D.1. Refer to chapter for
additional grounding recommendations.

Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit
or equivalent attenuation.

Allowable cable length in table D.1 is not exceeded.

Table D.1 – Allowable Cable Length

1

Filter Type

EN61800-3

First Environment

3

Restricted Distribution

or Second Environment

EN61800-3

First Environment

Unrestricted

Distribution

4

Integral

5 meters (16 feet)

1 meter (3 feet)

External - Short

2

5 meters (16 feet)

1 meter (3 feet)

External - Long

2

100 meters (328 feet)

5 meters (16 feet)

1

Testing of longer cable lengths is pending.

2

Contact Reliance Electric for details on optional external filters.