Parameter Descriptions

9-17

Sets the highest voltage the drive will output.

Maximum output current allowed before current limiting occurs.

Drive provides Class 10 motor overload protection. Settings 0-2
select the derating factor for the I

2

t overload function. See figure

9.8.

A088 Maximum Voltage

Range:

20 to Drive Rated Volts

Default:

Drive Rated Volts

See also:

N/A

A089 Current Limit

Range:

0.1 to (Drive Rated Amps x 1.8)

Default:

Drive Rated Amps x 1.8

See also:

N/A

A090 Motor OL Select

Range:

0 = No Derate
1 = Minimum Derate
2 = Maximum Derate

Default:

0 = No Derate

See also:

P032