Ppendix, Technical specifications – FanAm MD60 AC Drive User Manual

Page 93

Advertising
background image

Technical Specifications

A-1

A

PPENDIX

A

Technical Specifications

Environment

Altitude:

1000 m (3300 ft) maximum without derating

Ambient Operating
Temperature
Without Derating:

IP 20: -10° C (14° F) to 50° C (122° F)
NEMA 1/IP30: -10° C (14° F) to 40° C (104° F)

Storage
Temperature (all
const.):

-40° C (-40° F) to 85° C (185° F)

Relative Humidity:

0% to 95%, non-condensing

Shock (Operating):

15 G peak for 11 ms duration (+/-1.0 ms)

Vibration
(Operating):

1 G peak, 5 to 2000 Hz

Control

Carrier Frequency:

2-16 kHz. Drive rating based on 4 kHz.

Frequency Accuracy • Digital Input: Within +/-0.05% of set output

frequency.

• Analog Input: Within 0.5% of maximum output

frequency.

Speed Regulation -
Open Loop with Slip
Compensation:

+/-2% of base speed across a 40:1 speed range.

Stop Modes:

Multiple programmable stop modes including: Ramp,
Coast, DC-Brake, Ramp-to-Hold, and S Curve.

Accel/Decel:

Two independently programmable accel and decel
times. Each time may be programmed from 0-600
seconds in 0.1 second increments.

Intermittent
Overload

• 150% Overload capability for up to 1 minute.

• 200% Overload capacity for up to 3 seconds

Electronic Motor
Overload Protection:

Class 10 protection with speed-sensitive response.

Advertising