Technical Specifications

A-3

Under Voltage:

• 100-120 V AC Input – Trip occurs at 210 V DC bus

voltage (equivalent to 75 V AC incoming line)

• 200-240 V AC Input – Trip occurs at 210 V DC bus

voltage (equivalent to 150 V AC incoming line

• 380-480 V AC Input – Trip occurs at 390 V DC bus

voltage (equivalent to 275 V AC incoming line)

Control Ride-
Through:

Minimum ride-through is 0.5 sec - typical value 2 sec

Faultless Power
Ride-Through:

100 milliseconds

Dynamic Braking

Internal brake IGBT included with all ratings.

Approvals

UL

®

LIST

ED 966X

IND

CO N T E Q

UL508C

UL

®

LIST

ED 966X

IND

CO N T E Q

C

CSA 22.2

EMC Directive 89/336

LV:

EN 50178, EN 60204

EMC: EN 61800-3, EN 50081-1, EN 50082-2